Ammonia tank are considered critical unit in Petrochemical Plant due to their potential for leakage and explosion. To evaluate secondary effects, by PHAST It was determined that in the 50 mm ammonia leakage scenario during spring, an explosion would cause severe damage to equipment at distance of 75 m within an 18 m radius. If Hydrogen or fuel storage tanks are located within this zone, the likelihood of secondary explosions becomes high. Simulation results indicated that placing such units at a minimum safe distance of 38 m can prevent these outcomes. Furthermore, considering that flammability concentration of ammonia (160000 ppm), it can be concluded that in the 20 mm and 50 mm leakage scenarios, the ammonia cloud may ignite up to distances of 37 m and 52 m, respectively, in the worst case. Therefore, all heat and ignition sources must be positioned at a safe distance from the ammonia tank.